Cummins Diesel Generators 7.5 / 10 KVA

Acoustic enclosure:


The acoustic enclosure is made of 2 mm thick CRCA sheets and structural/ sheet metal base frame painted in Munsel green shade. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75 dBA at 1mtr sound levels specified by Ministry of Environment & Forest.


The enclosure has the following features:

  • Specially designed to meet stringent MOEF/ CPCB norms of 75 dBA @ lmtr at 75% load under free field conditions
  • Single point lifting for easy handling at customer site
  • Designed to have optimum serviceability
  • Air inlet louvers specially designed to operate at rated load
  • Made on special purpose CNC machines for consistency in quality and workmanship
  • Powder coated for long lasting service life and superior finish
  • With UV resistant powder coating, can withstand extreme environments
  • Use of special hardware for longer life
  • Insulation material meets exacting IS 8183 specifications for better sound attenuation
  • Flush styling - no projections
  • Fluid drains for lube oil and fuel on engine
  • Fuel filling point onside canopy
Cummins Diesel Generator, Cummins Diesel Generator Dealers

Technical data

Generator set specifications
Model C 7.5 D5 C 10 D5
Prime Power Rating KVA/KW 1 phase - 7.5/7.5 & 3 phase - 7.5/6 1 phase - 7.5/7.5 & 3 phase - 7.5/6
current(Amps) 1 phase - 26 & 3 phase - 10.5 1 phase - 34.78 & 3 phase - 14
Power Factor 1 phase - 1.0 & 3 phase - 0.8 (lag) 1 phase - 10 & 3 phase - 0.8 (lag)
No. of Phases 1 phase/3 phase 1 phase/3 phase

Enqine specifications
Make Cummins Cummins
Model X 1.3 G2 X 1.3 G2
BHP 15.78 15.78
Cooling Water Cooled Water Cooled
Aspiration Natural Natural
No. of Cylinders 2 2
RPM 1500 1500
Bore (mm) x Stroke (mm) 95 x 91 95 x 91
Compression Ratio 18.1 (+- 0.3):1 18.1 (+- 0.3):1
Displacement (ltrs.) 1.29 1.29
Ful HSD HSD
Fuel sumption(Ltr/hr)@75%
Lod with Radiator & Fan
2.4 2.7
Governor Electronic Electronic
Starting System 12 V Electrical 12 V Electrical
Lube oil Specification CH4 15W40 CH4 15W40
Lube oil Sump Capacity(Ltrs.) 4 4
Lube oil consumption(LPH) 0.3 % of fuel consumption 0.3 % of fuel consumption
Total Coolant Capacity(Ltrs) 4.65 4.65
Exhaust Pipe Size (mm) 34.1 34.1
Battery Capacity / Rating 32 Ah 12 V 32 Ah 12V

Alternator specifications
Make (Brand) CGT (Stamford) CGT(Stamford)
Enclosure IP 23 IP 23
Voltage Regulation (max) +/- 1% +/- 1%
Class of insulation H Class H Class
RPM / Frequency 1500/50 Hz 1500/50 Hz
Power Factor 0.8 (lag) 0.8 (lag)
No. of Phases 3 phase 1 phase 3 phase 1 phase
Frame Size PI 044 D PI 044 F PI 044 E 1 phase
Voltage 415 V 230 V 415 V 230 V
REcommended Cable size sq.mm.x No. of Runs (Allum. Armoured AYFY 3 1/2 Core 6 x 1 35 x 1 10 x 1 50 x 1